Facility | |
---|---|
Building | 3 buildings with 11+ floors each |
Capacity | 3,000 racks |
Floor Loading | 400~700 kg/m2 |
Seismic Rating | 225~338gal |
Raised Floor Height | 25-55cm |
Rack Size | 45U (120cm x 60cm) 42U (90-120cm x 60cm) |
Power | |
---|---|
Generator | N+1 |
UPS | 2N |
Power Provision | Support 3-4KW primary and redundant or 2KW primary configurations for standard racks. |
Fuel Storage | 18-36 hours (depends on the loading) |
Rack PDU Spec | NEMA 5-15R / L5-30R / L6-30R |
Security | |
---|---|
Security Officers | 7x24 |
Cameras | 24-hour surveillance video, 6 months for entrance and exit images, 3 months for other images |
Access Control | Key cards and biometric scanners |
Fire Detection | VESDA |
Fire Suppression | HFC-227ea、FM200、NAFS-125 |
Connectivity & Service | |
---|---|
Networks | HiNet backbone nodes, DCI (Data center Interconnect) |
Diversity | 1 entry point with single in-building path |
Carrier Availability | Project application |
Cloud Access | N/A |
Smart Hands | 7x24 |